Description |
Catalog Number |
SDN 2.5-24-100P |
SDN 4-24-100LP |
SDN 5-24-100P |
SDN 10-24-100P |
SDN 20-24-100P |
|
Input |
Nominal Voltage |
115/230 Vac auto select |
-AC Range |
85-132/176-264 Vac |
-DC Range1 |
90-375 Vdc |
210-375 Vdc |
N/A |
-Frequency |
47 - 63 Hz |
Nominal Current2 |
1.3 A. / 0.7 A |
2.1 A / 1.0 A |
2.2 A / 1.0 A |
5 A / 2 A typ. |
9 A/ 3.9 A |
-Inrush current max. |
typ. < 25 A |
typ. < 20 A |
typ. < 40 A |
Efficiency (Losses3) |
> 87.5% typ. (8.6 W) |
> 88% typ. (13.1 W) |
> 88% typ. (16.4 W) |
> 88% typ. (32.7 W) |
> 90% typ. (48 W) |
Power Factor Correction |
Units Fulfill EN61000-3-2 |
|
Output |
Nominal Voltage |
24 Vdc (22.5 - 28.5 Vdc adj.) |
24 Vdc (22.5 - 25.5 Vdc adj.) |
24 Vdc (22.5 - 28.5 Vdc adj.) |
-Tolerance |
< ±2% overall (combination Line, load, time and temperature related changes) |
-Ripple4 |
< 50 mVpp |
Overvoltage Protection |
> 30 Vdc, but < 33 Vdc, auto recovery |
Nominal Current |
2.5 A (60 W) |
3.8 A (92 W) |
5 A (120 W) |
10 A (240 W) |
20 A (480 W) |
-Current Limit |
Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current) |
Holdup Time5 |
> 50 ms |
> 100 ms |
> 100 ms |
> 100 ms |
Parallel Operation |
Single
or Parallel use is selectable via Front Panel Switch (SDN 2.5, 4 should
not be used in parallel as Class 2 rating would be violated.) |
|
General |
EMC: -Emissions |
EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A. |
-Immunity |
EN61000-6-1,
-2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3;
EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation
Class 4, EN61000-4-11; |
Approvals |
EN60950;
UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC).
EN61000-3-2, IEC60079-15 (Class 1, Zone 2, Hazardous Location, Groups A,
B, C, D w/ T3A temp class up to 60°C Ambient.) SEMI F47 Sag Immunity.
SDN 2.5 & SDN 4 - UL60950 testing to include approval as Class 2 power supply in accordance with UL1310. |
Temperature |
Storage: -25oC...+85oC Operation. -10°-60oC full power with operation to 70°C possible with a linear derating to half power from 60oC to 70oC
(Convection cooling, no forced air required). Operation up to 50% load
permissible with sideways or front side up mounting orientation. The
relative humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3. |
Humidity |
|
MTBF: |
> 820,000 hours |
> 640,000 hours |
> 600,000 hours |
> 510,000 hours |
- Standard |
Bellcore Issue 6 Method 1 Case 3 @ 40oC |
MIL STD 217F @ 30oC |
Warranty |
5 years |
General Protection/ Safety |
Protected
against continuous short-circuit, overload, open-circuit. Protection
Class 1 (IEC536), degree of protection IP20 (IEC 529) Safe low voltage:
SELV (acc. EN60950) |
Status Indicators |
Green LED and DC OK signal (N.O. Solid State Contact rated 200 mA / 60 Vdc) |
|
Installation |
Fusing -Input |
Internally fused. External 10 A slow acting fusing for the input is recommended to protect input wiring. |
-Output |
Outputs
are capable of providing high currents for short periods of time for
inductive load startup or switching. Fusing may be required for
wire/loads if 2x Nominal O/P current rating cannot be tolerated.
Continuous current overload allows for reliable fuse tripping. |
Mounting |
Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required). |
Connections |
Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: Two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid conductors. |
Case |
Fully enclosed metal housing with fine ventilation grid to keep out small parts. |
-Free Space |
25 mm above and below, 25 mm left and right, 10 mm in front |
25 mm above and below, 25 mm left and right, 15 mm in front |
70 mm above and below, 25 mm left and right, 15 mm in front |
H x W x D (inches/mm) |
4.88. x 1.97 x 4.55 (124 x 50 x 116) |
4.88 x 2.56 x 4.55 (124 x 65 x 116) |
4.88 x 3.26 x 4.55 (124 x 83 x 116) |
4.88 x 6.88 x 4.55 (124 x 175 x 116) |
Weight (lbs/kg) |
1 lbs (.45 kg) |
1.5 lbs (.68 kg) |
2.2 lbs (0.1 kg) |
3 lbs (1.36 kg) |