SDP Low Power DIN Rail Series
The compact, lightweight DIN Rail power supplies come in output voltages from 5 to 48 VDC and power ratings of up to 100 Watts. These extra small, efficient units are designed specifically for the industrial environment. Each unit is rated from -10ºC to 70ºC, with no derating necessary until after 60ºC.
Many extra “industrial” features are standard for the SDP. PowerBoost™ overload circuitry can start up industrial loads (i.e. motors, relays, solenoids and DC-DC converters), that can cause ordinary power supplies to foldback or shutdown. Each unit contains a DC indicator and front panel adjustment potentiometer. With the Sola SDP series, you can count on a high grade design.
|
|
|
|
Many extra “industrial” features are standard for the SDP-T. PowerBoostTM overload circuitry can start up industrial loads (i.e. motors, relays, solenoids and DC-DC converters), that can cause ordinary power supplies to foldback or shutdown. Each unit contains a DC indicator and front panel adjustment potentiometer. With the Sola SDP-T series, you can count on a high grade design. |
- Ultra slim 15W footprint
- No tools required for mounting
- Adjustable output
- PowerBoost™ industrial overload design
- Overvoltage, short circuit protection
- NEC Class 2 current limited
- Continuous short circuit protection
- Low output noise
- Screw terminal connections
- Industrial control
- Process control
- Machine control
- Building Automation
- Instrumentation
48-56 V 24-28 V
Catalog Number |
DC Output Voltage |
Output Current |
Ripple/Noise |
Size (H x W x D) |
SDP5-5-100T |
5-6 V |
5 A |
<50 mVpp |
2.95" x 1.77" x 3.58" 75 mm x 45 mm x 91 mm |
SDP2-12-100T |
10-12 V |
3.0 - 2.5 A |
SDP3-15-100T |
12-15 V |
4.2-3.4 A |
SDP1-48-100T |
1 A |
SDP06-24-100T |
0.6 A |
2.95" x 0.9" x 3.8" 75 mm x 22.8 mm x 96.7 mm |
SDP1-24-100T |
1.3 A |
2.95" x 1.77" x 3.58" 75 mm x 45 mm x 91 mm |
SDP2-24-100T |
2.1 A |
SDP4-24-100LT |
3.8A |
2.95" x 2.85" x 3.8" 75 mm x 72.5 mm x 96.7 mm |
SDP4-24-100RT* |
Description |
Catalog Number |
SDP06-24-100T |
SDP1-24-100T |
SDP2-24-100T |
SDP4-24-100RT |
SDP4-24-100LT |
List Price ($ USD) |
69.00 |
99.00 |
129.00 |
169.00 |
169.00 |
Input |
Input Voltage |
85-264 VAC, 90-375 VDC |
AC 85-132 / 176-264 (Auto Select) or DC 210-375 V |
Input Frequency |
43-67 Hz |
Input Current |
0.4 A / 0.25A |
0.7A / 0.4A |
1.1A / 0.7A |
2.2 A / 1.2 A |
External Fusing |
Not required. Unit provides internal fuse (T3A, not accessible) |
Hold-Up Time |
>25 ms |
Efficiency |
> 80% typ. |
> 83% typ. |
> 86% typ. |
> 88% typ. |
Losses |
< 3.75 W typ. |
< 6.1 W typ. |
< 8.1 W typ. |
< 12 W typ. |
Output |
Output Voltage |
24 V (22.5-28.5 VDC adj.) |
Voltage Regulation |
Static 0.5% Vout , dynamic +2% Vout overall |
Ripple/Noise1 |
< 50 mVpp |
Overvoltage Protection (OVP) |
> 30 VDC, but < 33 VDC, auto recovery |
Output Noise Suppression |
Radiated EMI values below EN61000-6-2 |
Rated Continuous Loading |
0.63 A @ 24 VDC, 0.54 A @ 28 VDC |
1.3 A @ 24 VDC, 1.1 A @ 28 VDC |
2.1 A @ 24 VDC, 1.8 A @ 28 VDC |
4.2 A @ 24.5 VDC 3.6 A @ 28 VDC |
3.8A @ 24.5 VDC |
Overload Behavior |
Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous. |
Protection |
Unit is continuously protected against short-circuit, overload and open-circuit. |
Power Back Immunity |
35 V |
Installation |
Case & Mounting |
Molded plastic housing using UL 94 approved flameproof material rating 94V-2. Simple snap-on to DINTS35/7.5 or TS35/15 rail system. |
Status Indicators |
Green LED on when Vout = “OK”. |
Dimensions (in/mm)(H x W x D) |
2.95 in x 0.9in x 3.8in 75 mm x 22.8 mm x 96.7 mm |
2.95 in x 1.77 in x 3.58 in 75 mm x 45 mm x 91 mm |
2.95 in x 2.85 in x 3.8 in 75 mm x 72.55 mm x 96.7 mm |
Weight (lbs/g) |
0.35 lbs (150 g) |
0.5 lbs (240 g) |
0.7 lbs (320 g) |
Mounting Orientation |
Standard: Vertical Optional: Horizontal or On Top (Contact Technical Services) |
Ventilation/Cooling •Free space for cooling |
Normal convection, no fan reqiured Above/below: 25 mm recommended |
Connection •Connector size range |
Input: screw terminals, connector size range: 20-12AWG (1.5-6mm2) for solid or stranded conductors. |
General |
Temperature |
Storage: -25°C...+85°C Operation. -10°-60°C full power with linear derating to half power from 60°C to 70°C. (Convection cooling, no forced air required). |
MTBF |
> 500,000 hrs according to Telcordia/Bellcore Document SR-332, Issue 1 |
Humidity |
Up to 90% noncondensing, IEC 68-2-2, 68-2-3 |
Electromagnetic Emissions (EME) |
EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55022) incl. Annex A |
Electromagnetic Immunity (EMI) |
EN 61000-6-2 (Includes EN 61000-6-1) (EN55024) Criterion A: no degradation of performance. |
Safe Low Voltage |
SELV (acc.EN60950) |
Prot. Class/ Voltage |
IP20 (IEC529), Protection Class 1 (IEC536) |
Warranty |
3 years |
Safety |
CB Scheme, EN60950, EN50178, EN60204, EN60079-15 (Class 1, Zone 2 Hazardous Locations, Temp Class T3), UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23 & 93/68/EEC). (EMC 89/336 & 93/68/EEC). EN61000-3-2, NEC Class 2 power supply acc. To NFPA 70 art. 725-41 (a)(2).2 |
Note:
1. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor. 2. For models less than 100W. |
Description |
Catalog Number |
SDP 5-5-100T |
SDP 2-12-100T |
SDP 3-15-100T |
SDP1-48-100T |
List Price ($USD) |
110.00 |
123.00 |
136.00 |
124.00 |
Input |
Input Voltage |
85-264 VAC, 90-375 VDC |
Input Frequency |
43-67 Hz |
Input Current |
0.6A @ 102 VAC 0.33A @ 196 VAC |
<1.0 A @ 102 VAC <0.6 A @ 196 VAC |
<1.0 A @ 100 VAC <0.6 A @ 196 VAC |
External Fusing |
Not required. Unit provides internal fuse (T3A, not accessible) |
Hold-Up Time |
> 25 ms |
Efficiency |
> 80% typ. |
> 86% typ. |
90% typ. |
Losses |
7.5 W typ. |
8.1W typ. |
Output |
Output Voltage |
5-5.5 VDC (5-6 min adj.) |
12 VDC (9.9-12.1 min adj.) |
15 VDC (11.9-15.1 min adj.) |
48 VDC (48-56 min adj.) |
Voltage Regulation |
< 2& Dynamic; < 0.5% Static |
Ripple/Noise1 |
< 50 mVpp |
Overvoltage Protection (OVP) |
< 6.7 VDC |
< 18 VDC |
< 20 VDC |
< 60 VDC |
Output Noise Suppression |
Radiated EMI values below EN61000-6-2 |
Rated Continuous Loading |
Iout 5A @ Vout = 5.1 V |
3 A @ 10 VDC, 2.5 A @ 12 VDC |
4.2 A @ 12 VDC, 3.4 A @ 15 VDC |
Up to 1.05 A @ 48 V 0.9 A @ 56 V |
Overload Behavior |
Continuous operation at overload/short-circuit: up to 1.5x Nominal Current Continuous. |
Protection |
Unit is continuously protected against short-circuit, overload and open-circuit.
|
Power Back Immunity |
10 V |
22 V |
80 V |
Installation |
Case & Mounting |
Molded plastic housing using UL 94 approved flameproof material rating 94V-2. Simple snap-on to DINTS35/7.5 or TS35/15 rail system. |
Status Indicators |
Green LED on when Vout = “OK”. |
Dimensions (in/mm) (H x W x D) |
2.95 in. x 1.77 in. x 3.58 in. 75mm x 45 mm x 91mm |
Weight (lbs/g) |
0.5 lbs (240 g) |
Mounting Orientation |
Standard: Vertical Optional: Horizontal or On Top (Contact Technical Services). |
Ventilation/Cooling •Free space for cooling |
Normal convection, no fan reqiured. Above/below: 25 mm recommended. |
Connection •Connector size range |
Input: screw terminals, connector size range: 20-12 AWG (1.5-6mm2) for solid or stranded conductors. |
General |
Temperature |
Storage: -25°C...+85°C Operation. -10°-60°C full power with operation to 70°C possible with a linear derating to half power from 60°C to 70°C. (Convection cooling, no forced air required). |
MTBF |
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1 |
Humidity |
Up to 90% RH, noncondensing, IEC 68-2-2, 68-2-3 |
Electromagnetic Emissions (EME) |
EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55022) incl. Annex A |
Electromagnetic Immunity (EMI) |
EN 61000-6-2 (Includes EN 61000-6-1) (EN55024) Criterion A: no degradation of performance. |
Safe Low Voltage |
SELV (acc. EN60950) |
Prot. Class/ Voltage |
IP20 (IEC529), Protection Class 1 (IEC536) |
Warranty |
3 years |
|
|
|
|
|
|
|