View CartMy Account / Order StatusHelp

Join our mailing list!







Google

(0 Item $0.00) 

  Home > Power Supplies > Sola Heavy Duty > Sola Power Supplies > SDP Low Power DIN Rail Series >

Sola SDP2-24-100T 50W 24V DIN PLACTIC 115/230VIN

SDP2-24-100T
Sola SDP2-24-100T 50W 24V DIN PLACTIC 115/230VIN


 
SDP2-24-100T
List Price: $167.66
Our Price: $142.51
You save $25.15!
Manufacturer: Sola Hevi Duty

Product Code: SDP2-24-100T
Qty:

Description
 
SDP Low Power DIN Rail Series

The compact, lightweight DIN Rail power supplies come in output voltages from 5 to 48 VDC and power ratings of up to 100 Watts. These extra small, efficient units are designed specifically for the industrial environment. Each unit is rated from -10ºC to 70ºC, with no derating necessary until after 60ºC.

Many extra “industrial” features are standard for the SDP. PowerBoost™ overload circuitry can start up industrial loads (i.e. motors, relays, solenoids and DC-DC converters), that can cause ordinary power supplies to foldback or shutdown. Each unit contains a DC indicator and front panel adjustment potentiometer. With the Sola SDP series, you can count on a high grade design.

 


Many extra “industrial” features are standard for the SDP-T. PowerBoostTM overload circuitry can start up industrial loads (i.e. motors, relays, solenoids and DC-DC converters), that can cause ordinary power supplies to foldback or shutdown. Each unit contains a DC indicator and front panel adjustment potentiometer. With the Sola SDP-T series, you can count on a high grade design.

 

Features
  • Ultra slim 15W footprint
  • No tools required for mounting
  • Adjustable output
  • PowerBoost™ industrial overload design
  • Overvoltage, short circuit protection
  • NEC Class 2 current limited
  • Continuous short circuit protection
  • Low output noise
  • Screw terminal connections

 

Applications
  • Industrial control
  • Process control
  • Machine control
  • Building Automation
  • Instrumentation
Selection Table

48-56 V
24-28 V
Catalog 
Number
DC Output Voltage
Output Current
Ripple/Noise
Size (H x W x D)
 SDP5-5-100T
5-6 V
5 A
<50 mVpp
2.95" x 1.77" x 3.58"
75 mm x 45 mm x 91 mm
 SDP2-12-100T
10-12 V
3.0 - 2.5 A
 SDP3-15-100T
12-15 V
4.2-3.4 A
 SDP1-48-100T
1 A
 SDP06-24-100T
0.6 A
2.95" x 0.9" x 3.8"
75 mm x 22.8 mm x 96.7 mm
 SDP1-24-100T
1.3 A
2.95" x 1.77" x 3.58"
75 mm x 45 mm x 91 mm
 SDP2-24-100T
2.1 A
 SDP4-24-100LT
3.8A
2.95" x 2.85" x 3.8"
75 mm x 72.5 mm x 96.7 mm
 SDP4-24-100RT*

 

Description

Catalog Number

SDP06-24-100T

SDP1-24-100T

SDP2-24-100T

SDP4-24-100RT SDP4-24-100LT
 List Price ($ USD) 69.00  99.00 129.00 169.00 169.00

Input

 Input Voltage 85-264 VAC, 90-375 VDC AC 85-132 / 176-264 
(Auto Select) or DC 210-375 V
 Input Frequency 43-67 Hz
 Input Current 0.4 A / 0.25A 0.7A / 0.4A

1.1A / 0.7A

2.2 A / 1.2 A
 External Fusing Not required. Unit provides internal fuse (T3A, not accessible)
 Hold-Up Time >25 ms
 Efficiency > 80% typ. > 83% typ. > 86% typ. > 88% typ.
 Losses < 3.75 W typ. < 6.1 W typ. < 8.1 W typ. < 12 W typ.

Output

 Output Voltage

24 V (22.5-28.5 VDC adj.)

 Voltage 
 Regulation

Static 0.5% Vout ,
dynamic +2% Vout overall

 Ripple/Noise1

< 50 mVpp

 Overvoltage
 Protection (OVP)

> 30 VDC, but < 33 VDC, auto recovery

 Output Noise
 Suppression

Radiated EMI values below EN61000-6-2

 Rated
 Continuous
 Loading
0.63 A @ 24 VDC,
0.54 A @ 28 VDC
1.3 A @ 24 VDC,
1.1 A @ 28 VDC
  2.1 A @ 24 VDC,
1.8 A @ 28 VDC
4.2 A @ 24.5 VDC
3.6 A @ 28 VDC
3.8A @ 24.5 VDC
 Overload
 Behavior

Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous.

 Protection

Unit is continuously protected against short-circuit, overload and open-circuit.

 Power Back Immunity 35 V

Installation

 Case & Mounting

Molded plastic housing using UL 94 approved flameproof material rating 94V-2. Simple snap-on to DINTS35/7.5 or TS35/15 rail system.

 Status Indicators

 Green LED on when Vout = “OK”.

 Dimensions 
 
(in/mm)(H x W x D)

 2.95 in x 0.9in x 3.8in
75 mm x 22.8 mm x 96.7 mm

 2.95 in x 1.77 in x 3.58 in
75 mm x 45 mm x 91 mm

2.95 in x 2.85 in x 3.8 in 
75 mm x 72.55 mm x 96.7 mm

 Weight (lbs/g)      0.35 lbs (150 g) 0.5 lbs (240 g)

0.7 lbs (320 g)

 Mounting
 Orientation  
 

Standard: Vertical
Optional: Horizontal or On Top (Contact Technical Services)

 Ventilation/Cooling
   •Free space
    for cooling

Normal convection, no fan reqiured
Above/below: 25 mm recommended

 Connection
   •Connector size
     range
 Input: screw terminals, connector size range: 20-12AWG (1.5-6mm2) for solid or stranded conductors.

General

 Temperature
 Storage: -25°C...+85°C Operation. -10°-60°C full power with linear derating to half power from 60°C to 70°C. (Convection cooling, no forced air required).
 MTBF        > 500,000 hrs according to Telcordia/Bellcore Document SR-332, Issue 1
 Humidity   

Up to 90% noncondensing, IEC 68-2-2, 68-2-3

 Electromagnetic
 Emissions (EME)   
 EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55022) incl. Annex A
 Electromagnetic 
 Immunity (EMI)   

 EN 61000-6-2 (Includes EN 61000-6-1) (EN55024) Criterion A: no degradation of performance.

 Safe Low Voltage  SELV (acc.EN60950) 
 Prot. Class/
 Voltage    
 IP20 (IEC529), Protection Class 1 (IEC536)
 Warranty

3 years

Safety

 CB Scheme, EN60950, EN50178, EN60204, EN60079-15 (Class 1, Zone 2 Hazardous Locations, Temp Class T3), UL508 Listed, cULus, UL 60950,  cURus, CE (LVD 73/23 & 93/68/EEC). (EMC 89/336 & 93/68/EEC). EN61000-3-2, NEC Class 2 power supply acc. To NFPA 70 art. 725-41 (a)(2).2              
 Note:

 1. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
 2. For models less than 100W.

Other Voltages

 

Description

Catalog Number

SDP 5-5-100T

SDP 2-12-100T SDP 3-15-100T

SDP1-48-100T

 List Price ($USD) 110.00 123.00 136.00 124.00

Input

 Input Voltage 85-264 VAC, 90-375 VDC
 Input Frequency 43-67 Hz
 Input Current 0.6A @ 102 VAC
0.33A @ 196 VAC 
<1.0 A @ 102 VAC
<0.6 A @ 196 VAC

<1.0 A @ 100 VAC
<0.6 A @ 196 VAC

 External Fusing Not required. Unit provides internal fuse (T3A, not accessible)
 Hold-Up Time > 25 ms
 Efficiency > 80% typ. > 86% typ. 90% typ.
 Losses 7.5 W typ. 8.1W typ.

Output

 Output 
 Voltage
5-5.5 VDC (5-6 min adj.) 12 VDC (9.9-12.1 min adj.) 15 VDC (11.9-15.1 min adj.) 48 VDC (48-56 min adj.)
 Voltage 
 Regulation
< 2& Dynamic; < 0.5% Static
 Ripple/Noise1

< 50 mVpp

 Overvoltage
 Protection (OVP)
< 6.7 VDC

< 18 VDC

< 20 VDC

< 60 VDC

 Output Noise
 Suppression

Radiated EMI values below EN61000-6-2

 Rated
 Continuous
 Loading
Iout 5A @
Vout = 5.1 V
3 A @ 10 VDC,
2.5 A @ 12 VDC
4.2 A @ 12 VDC,
3.4 A @ 15 VDC
  Up to 1.05 A @ 48 V
0.9 A @ 56 V
 Overload
 Behavior

Continuous operation at overload/short-circuit: up to 1.5x Nominal Current Continuous.

 Protection

Unit is continuously protected against short-circuit, overload and open-circuit.

 Power Back
 Immunity
10 V 22 V 80 V

Installation

 Case & Mounting

Molded plastic housing using UL 94 approved flameproof material rating 94V-2. Simple snap-on to DINTS35/7.5 or TS35/15 rail system.

 Status Indicators
 Green LED on when Vout = “OK”.
 Dimensions 
 (in/mm) (H x W x D)

2.95 in. x 1.77 in. x 3.58 in.
75mm x 45 mm x 91mm

 Weight (lbs/g)      0.5 lbs (240 g)
 Mounting
 Orientation  
 

Standard: Vertical
Optional: Horizontal or On Top (Contact Technical Services).

 Ventilation/Cooling
  
•Free space for cooling

Normal convection, no fan reqiured.
Above/below: 25 mm recommended.

 Connection
  
•Connector size range

Input: screw terminals, connector size range: 20-12 AWG (1.5-6mm2) for solid or stranded conductors.

General

 Temperature
 Storage: -25°C...+85°C Operation. -10°-60°C full power with operation to 70°C possible 
 with a linear derating to half power from 60°C to 70°C. (Convection cooling, no forced air required).
 MTBF       
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1
 Humidity   

Up to 90% RH, noncondensing, IEC 68-2-2, 68-2-3

 Electromagnetic
 Emissions (EME)   
  EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55022) incl. Annex A
 Electromagnetic 
 Immunity (EMI)   

  EN 61000-6-2 (Includes EN 61000-6-1) (EN55024) Criterion A: no degradation of performance.

 Safe Low Voltage
 SELV (acc. EN60950)
 Prot. Class/
 Voltage    
 IP20 (IEC529), Protection Class 1 (IEC536)
 Warranty

3 years


Share your knowledge of this product with other customers... Be the first to write a review

Browse for more products in the same category as this item:

Power Supplies > Sola Heavy Duty > Sola Power Supplies > SDP Low Power DIN Rail Series
Power Supplies > Sola Heavy Duty > Sola Power Supplies
Wallco Industrial Electronics
53-55 E.Jackson St Wilkes-Barre, Pa 18701 Phone: 1800-392-5526
 About Us
 Become an Affiliate
 Privacy Policy
 Send Us Feedback
 
Company Info | Advertising | Category Index | Product Index | Help | Terms of Use
Copyright © 2013 Wallco Industrial Electronics. All Rights Reserved.
Wallco Industrial Electronics & Wallco Industrial Electronics Home Page